Forward Acting

FLCO (Flat Low-Pressure Composite)
FLCO (Flat Low-Pressure Composite) NA: Product Image
Downloads
  1. FLCO Specifications (pdf - 62.4Kb)
  2. FLCO Min.-Max. Table (pdf - 64Kb)
  3. FLCO Installation Guide (pdf - 74.4Kb)
  4. CE Marked FLCO Instructions (pdf - 37.3Kb)

Oseco's FLCO is easy to install and non-torque-sensitive.  This low-pressure disc is suggested for applications in which the normal operating pressure does not exceed 50% of the rated burst pressure.

Constructed with a metal center section of Nickel 200, Monel®-400, Inconel®-600 or 316 Stainless Steel, the section is lined on both sides with a fluoropolymer liner to form a corrosion barrier.  Klingersil C-4401 ring gaskets are standard and attached to both sides to from the completed assembly.

  • Sizes 2"-24" (consult factory for larger sizes)
  • No special holders required-fits between ANSI RF flanges
  • Non-torque-sensitive
  • Bi-directional (has same burst pressure in either direction)
  • Low-pressure relief
  • Burst Tolerance: ±5% 40 psig & up,  ±2 psig 3 psig up to 40 psig, +2, -0 psig Below 3 psig
  • Corrosion-resistant fluoropolymer in contact with all process media.
  • Damage-resistant
  • Choice of gasket materials
  • Maximum temperature 500º F
  • Optional integral sensor (FLCOS)